ETAL
ETAL EFS-V3 fuse switch disconnector
Made in EgyptIEC 60947-1 / -3
Fuse switch disconnectors

EFS-V3/250

Fuse switch disconnector

EFS-V3/250 fuse switch disconnector for size NT1 fuse links: 250 A rated operation current at 400 V AC (AC-23B), 3 poles, 18 W power loss, to IEC 60947-1 / -3.

Rated current
250A
Fuse size
NT1
Power loss
18W
Poles
3

Technical data

Technical specifications.

Ratings

Rated operation current
250A
Fuse size
NT1
Power loss
18W
Short-circuit capacity @ 400 V
≥ 50kA
Protected short-circuit making · Icw
120kA
Rated isolation voltage · Ui
1000V
Rated impulse withstand · Uimp
12kV
Fuse-link rated voltage · Ue
400V
Frequency
50/60Hz
Poles
3
Protection ON / OFF
IP20 / IP30
Standard
IEC 60947-1 / -3

Working conditions

Ambient temperature
−5 ~ +55 °C
Working mode
Continuous
Operation
Handle
Installation
Vertical
Altitude
≤ 2000 m
Pollution degree
3
Overvoltage level
IV

Selection table

Rated operation current.

By rated operational voltage (Ue) and utilization category.

UeUtilizationEFS-V3/250EFS-V3/400EFS-V3/630
400 V ACAC-23B250 A400 A630 A
500 V ACAC-22B250 A400 A630 A
690 V ACAC-21B200 A315 A500 A
  • Thermal current with fuse link (Ith) equals rated operation current (Ie).

Dimensions

Dimensional drawing

EFS-V3 fuse switch disconnector dimensional drawing (mm)
Width
100 mm
Depth
200 mm
Overall height
700 mm
Phase pitch
210 mm
Top to first terminal
70 mm
Bottom terminal offset
57 mm
Depth when open
340 mm
Opening angle
60°
Download drawing

Where it's used

Applications & sectors

  • Industrial
  • Oil & gas
  • Power distribution
  • Data centres
  • Rail & transport
  • Renewable energy

Supporting documents

Technical documents.

Download the datasheet, drawing and certificates for this product.

Browse full technical library

Next step

Proceed with documents or enquiry.

Share the required standard, quantity, or project deadline and ETAL will route your request to the right sales or engineering contact.